3) Locate the centering frame of the replacement fan on the
mounting lug of the SIMOTION D410-2.
4) Slide the replacement fan on the mounting lug into the
Control Unit.
Make
sure that the fan connector fits into the centering frame
of the the printed circuit board.
Engage both snap hooks on the fan in the housing of the
Control Unit.
8.2.5 Replacing the CompactFlash card
If spare parts are used, you must contact the Technical Support Center to transfer the license
key of the defective CompactFlash card to the new CompactFlash card.
Proceed as follows to write your project to the new CompactFlash card:
Changing the CompactFlash card (Page 291)
Writing to a CompactFlash card (Page 292)
Detailed information about licensing can be found:
In the
SIMOTION SCOUT
Configuration Manual
In the FAQs on the Internet (
http://support.automation.siemens.com/WW/view/en/
36947932)
Service and maintenance
8.2 Replacing modules
SIMOTION D410-2
268 Commissioning and Hardware Installation Manual, 01/2015

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D410-2 DP and is the answer not in the manual?

Siemens SIMOTION D410-2 DP Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D410-2 DP
CategoryController
LanguageEnglish

Related product manuals