Advanced commissioning
7.6 Basic positioner and position control
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
221
Defining the digital signals for controlling direct setpoint input
Precondition
You have selected the "Direct setpoint input (MDI)" screen.
Interconnect the signals to control the direct setpoint input using the appropriate signals from
your machine control.
Enables MDI. This bit must be = 1 if you control the converter using MDI.
ioning: Traverse the axis with position control using the target position.
1: Set up: Traverse the axis position
-controlled using velocity input
While operational, the axis operating mode can be switched over from "Set up" to "Pos
i-
If "Set up" is active, then the two bits ⑥ and ⑦ define the direction of travel.
0: The converter stops the axis and maintains the axis in position after standstill. The
actual traversing block still remains valid.
1: The axis continues the interrupted traversing block.
0: The converter stops the axis and maintains the axis in position after standstill. The
converter can no longer continue the actual traversing block.
1: Axis waits for a new start command.