Advanced commissioning
7.8 Application-specific functions
Converter with control units CU250D-2
254 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
p0490
1)
(factory setting 0000bin)
Using the 3rd bit of the parameter value, invert the input signals of digital input 3
p0580
1)
(factory setting 0)
Connect input of probe with a digital input.
p0581
1)
(factory setting 0)
Edge for analyzing the probe signal for measuring speed list value
0: 0/1 edge
p0582
1)
(factory setting 1)
Number of pulses per revolution
p0583
1)
(factory setting 10 s)
Maximum measurement time for the probe If there is no new pulse before the
maximum measuring time elapses, the inverter sets the actual speed value in
r0586 to zero.
The time is restarted with the next pulse.
p0585
1)
(factory setting 1)
The inverter multiplies the measured speed by the gear ratio before displaying it
r0586
1)
Result of the speed calculation
p2181
Response when evaluating the load monitor. For setting options, see Table 7-31
Response options for load monitoring (Page 254).
p2192
Load monitoring delay time
(factory setting 10 s)
Delay time for evaluating load monitoring.
p2193 = 2
For load monitoring configuration
,
see Table 7-30 Setting options for load monitoring (Page 250)
p3230 = 586
Load monitoring actual speed value
(factory setting 0)
Result of the speed calculation with the evaluation of the speed monitoring.
p3231
Load monitoring speed deviation
(factory setting 150 rpm)
Permissible speed deviation of load monitoring.
1)
The "Probe" subfunction calculates the speed from the pulse signal of the digital input.
For more information, see the List Manual (the parameter list and function diagram 8013).
Table 7- 31 Response options for load monitoring
Load monitoring deactivated (factory setting)
A07920 for torque/speed too low
A07921 for torque/speed too high
A07922 for torque/speed out of tolerance
F07923 for torque/speed too low
F07924 for torque/speed too high
F07925 for torque/speed out of tolerance