Advanced commissioning
7.9 Safe Torque Off (STO) safety function
Converter with control units CU250D-2
270 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Reduced acceptance after functions have been expanded
A full acceptance test is necessary only after first commissioning. A reduced acceptance test
is sufficient when safety functions are expanded.
Measure
Acceptance test
Acceptance test
Documentation
Functional expansion of the ma-
chine (additional drive).
Yes.
Only check the safety
functions of the new
drive.
Supplement machine overview
Supplement inverter data
Add function table
Log the new checksums
Countersignature
Transfer of inverter settings to
other identical machines by means
of series commissioning.
No.
Only check the control
of all of the safety
functions.
Add machine description
Check checksums
Check firmware versions
Documents for acceptance
The STARTER provides you with a number of documents to be regarded as a
recommendation for the acceptance tests of the safety functions.
Procedure
Proceed as follows to create the acceptance documentation for the drive using STARTER:
1. In STARTER, select "Create acceptance documentation":
STARTER has templates in German and English.