Commissioning
5.3 Basic commissioning with IOP
Converter with control units CU250D-2
66 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
5.
Select th
e correct frequency for your Inverter and at-
tached motor.
The use of the 87 Hz characteristic allows the motor to
operate at 1.73 times of its normal speed.
6.
A
t this stage the wizard will begin to ask for the data
relating specifically to the attached motor. The data is
obtained from the motor rating plate.
7.
The Moto
r Data screen indicates the frequency charac-
teristic of the attached motor.
8.
Input the correct Motor Voltage from the motor rating
plate.
9.
Input the correct Motor Current from the motor rating
plate.
10.
Input the correct P
ower Rating from the motor rating
plate.