EasyManua.ls Logo

Siemens SINAMICS G120D - Page 67

Siemens SINAMICS G120D
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
5.3 Basic commissioning with IOP
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
67
11.
Input the correct Motor Speed from the motor rating
plate.
This value is given in RPM.
12.
Select to run or disable Motor Data Identification fun
c-
tion.
This function, if active, will not start until the first run
command is given to the Inverter.
13.
Select either zero pulse on no zero pulse for the a
t-
tached encoder.
If no encoder is fitted to the motor, the option will not be
displayed.
14.
Enter the correct pulses per revolution for the encoder.
This information is normally printed on the casing of the
encoder.
15.
Select the macro that is suitable for your application.
Once selected all inputs, outputs, command sources
and setpoints will be automatically configured by the
software.
For further information see the section that details the
precise s
ettings for each macro. Please see installation
section of this manual.
16.
Set the Minimum Speed at which the attached motor
should run.

Table of Contents

Other manuals for Siemens SINAMICS G120D

Related product manuals