Subsequent damage after a full short-circuit trip of the circuit breaker
If, after a full short-circuit trip, the circuit breaker is closed again without first checking it, the
drive or the circuit breaker can be subsequently damaged.
Before reclosing the circuit breaker, carry out a voltage check and measure the resistance.
Provide the results of these measurements to the Service & Support organization. After the
Service & Support organization has checked the values, if necessary replace the vacuum
tubes of the circuit breaker.
Damage caused by incorrect parameter assignment
Malfunctions can occur if you change parameters.
Do not change the parameters, e.g. for the motor circuit-breaker.
Note
To complement these operating instructions, the List Manual contains an overview of all
parameters as well as a selection of function diagrams to describe the operating principle.
8.2 Operating the drive
Only trained personnel should be allowed to operate the drive.
This section describes basic operating procedures performed via the AOP30 operator panel.
8.3 Operation via the AOP30 operator panel
8.3.1 General information about the AOP30 operator panel
8.3.1.1 AOP30 operator panel
You can use the Advanced Operator Panel (AOP30) for operating and troubleshooting the
drive. The AOP30 communicates with the drive via a serial RS-232 interface with PPI protocol.
The interface is a point-to-point connection. The AOP30 has the master function in this
communication. The connected drive has the slave function.
Operation
8.3 Operation via the AOP30 operator panel
SINAMICS GM150 6SL3810-2LN31-8AA2
102 Operating Instructions Rev.201910281332 EXAMPLE