Preparations for use
4
When carrying out any work, carefully observe the information provided in Chapter "Safety
instructions (Page 17)".
4.1 Requirements for installation location
The cabinet units are suitable for installation in general operating areas (to
DIN EN 60146-1-1 / VDE 558 T11 and DIN EN 50178 / VDE 0160 (IEC 62103), degree of
contamination 2; without conducted contamination). For this reason, SINAMICS devices must
be protected in such a way that they cannot be touched directly when they are being installed
in general operating areas.
The operating areas must be dry and free of dust. The air supplied must not contain any
electrically conductive gas, vapors, or dust which could impair operation.
For information about permissible ambient and installation conditions, see the "Technical data
and drawings" section.
4.2 Inspections when receiving the delivery
4.2.1 Scope of delivery
The scope of delivery includes the following components:
Power unit, incl. closed-loop control
Excitation cabinet (can be ordered separately)
This option is required for controlling separately excited synchronous motors.
This documentation relates to the complete system.
SINAMICS GM150 6SL3810-2LN31-8AA2
Operating Instructions Rev.201910281332 EXAMPLE 57