EasyManua.ls Logo

Siemens SINAMICS GM150 - Anti-Condensation Heating (Option L55); EMERGENCY STOP Category 1 (Option L60); Uninterruptible Power Supply (UPS) (Option L53)

Siemens SINAMICS GM150
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.6.25 Uninterruptible power supply (UPS) (option L53)
The uninterruptible power supply (UPS) ensures that the control system continues to run
because the line voltage is protected. The following conditions must be met in order that the
drive can continue to operate:
The DC-link voltage does not undershoot the U
d min
limit
The medium-voltage switch does not switch off because of undervoltage.
If kinetic buffering is activated, drives with large moments of inertia can bridge voltage brown-
outs or short power failures. The kinetic buffering supports the DC-link voltage.
3.6.26 Anti-condensation heating (option L55)
The anti-condensation heating is used at low ambient temperatures and high levels of humidity
to prevent condensation from forming. The heating is controlled via a thermostat.
The number of anti-condensation heaters is set in accordance with the number of cabinet
panels.
The converter monitors and signals if the external supply for the anti-condensation heating fails.
See also
Safety instructions for maintenance (Page 169)
3.6.27 EMERGENCY STOP Category 1 (option L60)
Emergency Off, stop category1 (24 VDC) for controlled stop according to IEC60204.
In the standard version, Emergency Off stop category 0 is set for an uncontrolled stop. It also
has a function for disconnecting the drive from the power supply via the circuit-breaker. The
motor coasts down. The Emergency Off, stop category 1 function includes rapid stopping of the
drive using a deceleration ramp to be parameterized by the user. Voltage is then disconnected
from the drive as described for Emergency Off, stop category 0.
The EMERGENCY OFF button with protective collar is installed in the drive cabinet door.
Description
3.6 Description of options
SINAMICS GM150 6SL3810-2LN31-8AA2
Operating Instructions Rev.201910281332 EXAMPLE 51

Table of Contents

Other manuals for Siemens SINAMICS GM150

Related product manuals