7. You have two parameter selection options:
– All parameters of the selected DO
Press the <▼> function key to select "All parameters". Then confirm the selection with
OK. A list of all parameters of the selected DO is displayed.
– Selection of plausible parameters (see "List of the signals for the operation screen"
below) of the selected DO.
Select a parameter from the list of the signals for the operation screen of the selected DO.
The selected parameters from this list are displayed in the operation screen with an
abbreviated name (e.g. NSOLL).
8. Select the desired parameter or enter the parameter from the numeric keypad.
9. Confirm the setting by pressing the <OK> function key. The "Please wait" message appears
briefly. Then the operation screen appears in the configuration you set.
9(&725$86
3%62// ,B,67 $HII
$867 )B$86 +]
3:,5.N:
/7,7
+HOS
&KDQJH
6HO3DU
'LDJ
List of signals for the operation screen
Table 8-1 List of signals for the operation screen
Signal Parameter Short name Unit Scaling
(100% = ...)
DO: Vector MV
Factory setting (entry no.)
Speed setpoint upstream of RFG (1) r1114 NSETP 1/min p2000
Output frequency (2) r0024 F_OUT Hz Reference frequen‐
cy
Output smoothed (3) r0032 P_ACT kW r2004
DC-link voltage smoothed (4) r0026 UDC V p2001
Actual speed smoothed (5) r0021 N_ACT 1/min p2000
Actual absolute current smoothed (6) r0027 I_IST A p2002
Motor temperature (7) r0035 T_MOT °C Reference tempera‐
ture
Motor temperature (8) r0037 T_LT °C Reference tempera‐
ture
Actual torque smoothed (9) r0031 M_ACT Nm p2003
Drive output voltage smoothed (10) r0025 C_OUT V p2001
Speed setpoint smoothed r0020 NSETP 1/min p2000
Control factor smoothed r0028 % Reference control
factor
Field-producing current component r0029 A p2002
Torque-producing current component r0030 A p2002
Operation
8.3 Operation via the AOP30 operator panel
SINAMICS GM150 6SL3810-2LN31-8AA2
Operating Instructions Rev.201910281332 EXAMPLE 109