9.4.4.6 Checking the capacitor release
Check the following settings:
T950
Primary tapping: 400 V + 15%
Secondary side: jumpers 32 – 33
K950
Measuring-circuit voltage at IN3 (no-load voltage of the C release unit: approx. 320 V)
Switch positions: UNDERLOAD, NO MEMORY (the switches are located at the side).
T1 = 0.1 s
Ue = 30% / release at 180 V
Hysteresis = 5% / enable at 210 V
K951
Measuring-circuit voltage at IN2
Switch positions: UNDERLOAD, NO MEMORY (the switches are located at the side).
T1 = 0.1 s
Ue = 60% / release at 180 V
Hysteresis = 5% / enable at 202 V
The wiring to the circuit-breaker must be checked according to the circuit diagram.
9.4.4.7 Checking the cable and screw terminals
Check the cable and screw terminals regularly to ensure that they are secure.
Tighten the screws if necessary. When doing this, comply with the specified torques
(Page 187).
Check the cabling for defects.
Replace any defective parts immediately.
9.4.4.8 Checking the plug connections.
Regularly check the plug connections to ensure they are seated correctly and the contacts are
not corroded.
Note
The fiber-optic cables for the gating boards must be properly inserted in the connectors.
Maintenance
9.4 Inspection and maintenance
SINAMICS GM150 6SL3810-2LN31-8AA2