9.5.10 Door interlock system
Contact Technical Support (Page 205) if the door interlock system becomes defective.
9.5.11 Replacing the precharging transformer
WARNING
Danger to life as a result of incorrect replacing the precharging transformer
Replacing the precharging transformer incorrectly can result in death, serious injury, or
material damage.
Follow "the five safety rules (Page 17)".
Before replacing the precharging transformer, open the safety disconnector for the 400 V
supply.
Lift the transformer carefully because it is heavy (> 45 kg).
Removing the precharging transformer
1. Detach the high-voltage cables .
2. Detach the 400 V connecting cables .
3. Detach the grounding cable .
4. Remove the fixing screws at the front and rear on the base brackets.
5. Remove the transformer.