EasyManua.ls Logo

Siemens SINAMICS GM150 - Replacing the Back-Up Battery of the AOP30 Operator Panel

Siemens SINAMICS GM150
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Press the "F5" key ("Yes") on the AOP to confirm the selection of the new software version .
The firmware will be loaded. This procedure takes approx. five minutes.
Note
While loading, do not switch off the power supply for the drive and AOP.
If the loading process for the new firmware is not completed successfully because of a a
power outage or the connection process, the currently loaded firmware is retained. The
prompt appears at the next switch on.
If a power outage or aborted connection occurs during the last 20 seconds of the loading
process, the AOP firmware is destroyed. In this case, reload the firmware from the product
CD via the PC with "LOAD_AOP30".
Reloading the firmware
1. Establish the RS232 connection from the PC to the AOP30.
2. Switch on the 24 V power supply.
3. On the PC, launch the LOAD_AOP30 program.
4. Choose the PC interface (COM1, COM2).
5. Choose the firmware (AOP30.H86) and open the file.
6. Follow the instructions in the program status window. Switch on the AOP30 using the red
button (O). Loading begins.
9.4.8 Replacing the back-up battery of the AOP30 operator panel
Table 9-1 Technical specifications of the backup battery
Type CR2032 3V lithium battery
Manufacturer Maxell, Sony, Panasonic
Nominal capacity 220 mAh
Maximum permissible charging current 10 mA, limited to < 2 mA in the operator panel
Self-discharge at 20° C 1%/year
Service life in the backup mode > 1 year at 70° C; >1.5 years at 20° C
Service life in operation > 2 years
Replacing the backup battery
1. Switch off the main circuit-breaker.
2. Open the cabinet.
3. Disconnect the 24 VDC power supply and communications line on the operator panel.
4. Open the cover of the battery compartment.
5. Remove the old battery.
Maintenance
9.4 Inspection and maintenance
SINAMICS GM150 6SL3810-2LN31-8AA2
Operating Instructions Rev.201910281332 EXAMPLE 185

Table of Contents

Other manuals for Siemens SINAMICS GM150

Related product manuals