Saving LOCAL mode
Setting "Yes"(default setting):
The LOCAL operating status is saved when the power supply is switched off and restored
the next time power is switched on.
Setting "No":
The REMOTE operating status is activated when the supply voltage is switched back on.
Off in remote
Setting "Yes":
It is possible to switch off in remote mode by pressing the<OFF> key.
Setting "No":
The <OFF> key has no effect in remote operation.
The<OFF> key is always active in LOCAL mode.
LOCAL/REMOTE also during operation
Setting "Yes":
You can switch between LOCAL and REMOTE when the drive is switched on (i.e. motor is
running).
Setting "No" (default setting):
Before the system switches to LOCAL, a check is carried out to determine whether the drive
is in the operational status. In this case, the system does not switch to LOCAL and outputs
the error message "Local mode during operation not possible". Before the system switches
to REMOTE, the drive is switched off and the setpoint is set to 0.
Red OFF key acts as
OFF1 - Ramp-down on the deceleration ramp (p1121). OFF1 is the default setting.
OFF2 - Immediate pulse block, motor coasts to a standstill.
OFF3 - Ramp-down on the emergency stop ramp (p1135).
The OFF key is only effective in LOCAL mode.
Red OFF key also in REMOTE
Setting "Yes":
It is possible to switch off in remote mode by pressing the<OFF> key.
Setting "No":
The <OFF> key has no effect in REMOTE operation.
In LOCAL mode, the OFF key is always in effect.
Operation
8.3 Operation via the AOP30 operator panel
SINAMICS GM150 6SL3810-2LN31-8AA2
112 Operating Instructions Rev.201910281332 EXAMPLE