Communication via PROFINET IO
5.6 Communication via PROFINET Gate
Communication
138 Function Manual, 12/2018, 6SL3097-5BD00-0BP0
5.6.2 Preconditions for PN Gate
Hardware
SINAMICS CU320-2 PN with firmware version as of 4.5
Communication Board Ethernet 20 (CBE20)
Short Ethernet cable to connect CBE20 and CU320-2 PN (X150)
Recommendation: Ethernet cable with the article number: 6SL3060-4AB00-0AA0
Control hardware with standard Ethernet interface (100 Mbit/s or higher),
for example, the SIMATIC Box IPC 427C.
Note
The Gate PC must guarantee the short latency times required for operating the PN Gate.
Influencing variables are the CPU performance, mainboard hardware (Ethernet chipset and
its connection), and the BIOS and the software components involved
(operating system
components such as memory mapping, Ethernet driver, interrupt link, configuration).
Software
STARTER as of V4.3
Note
Startdrive
Please note that you still cannot use this function with Startdrive.
or
Drive ES as of V5.5
or
SIMATIC STEP 7 as of V5.5 SP2
Development kit for the development and configuration:
SINAMICS PN Gate DevKit (Article No. 6SL3071-0CA00-0XA0)
Licenses
The PN Gate CU requires a runtime license with Article No. 6SL3074-0AA03-0AA0 or
the Z option G01 for CFC.
PROFINET version
SINAMICS PN Gate V2 is compatible with PROFINET V2.2