Communication via Ethernet/IP (EIP)
7.7 Integrating the drive device into the EIP network via DHCP
Communication
200 Function Manual, 12/2018, 6SL3097-5BD00-0BP0
7.7 Integrating the drive device into the EIP network via DHCP
Integrating the drive via the PROFINET onboard interface X150 into the EIP network
Proceed as follows to integrate the drive into the EIP network:
1. Set p8924 (PN DHCP mode) = 2 or 3
Parameterization
Meaning
p8924 = 2
The DHCP server assigns the IP address based on the MAC address.
p8924 = 3 The DHCP server assigns the IP address based on the station name.
2. Save the settings with p8925 = 2.
The next time that it is run-up, the drive retrieves the IP address made available by a
DHCP server. After the drive has run-up, you can address the drive as Ethernet
participant.
Note
Immediate switchover without restart
The switchover to
DHCP is performed immediately and without a restart if the change is
carried out with the EIP command "Set Attribute Single" (class F5 hex, attribute 3), e.g.
using:
An EIP control
An EIP commissioning tool
Result:
You have integrated the drive into the EIP network via DHCP.
Displays
r8930: Station name of the onboard PROFINET interface X150
r8934: DHCP mode of the onboard PROFINET interface X150
r8935: MAC address of the onboard PROFINET interface X150