Communication according to PROFIdrive
3.4 Acyclic communication
Communication
62 Function Manual, 12/2018, 6SL3097-5BD00-0BP0
3.4.5 Example 2: Writing parameters (multi-parameter request)
Requirements
The PROFIdrive controller has been commissioned and is fully operational.
PROFIdrive communication between the controller and the device is operational.
The controller can read and write data sets in conformance with PROFINET/PROFIBUS.
Special requirements for this example:
Servo control or vector control with activated "Extended setpoint channel" function
module
Task description
Jog 1 and 2 are to be set up for drive 2 (also drive object number 2) via the input terminals of
the Control Unit. A parameter request is to be used to write the corresponding parameters as
follows:
BI: p1055 = r0722.4
Jog bit 0
BI: p1056 = r0722.5
Jog bit 1
p1058 = 300 rpm
Jog 1 speed setpoint
p1059 = 600 rpm
Jog 2 speed setpoint
The request is to be handled using a request and response data block.
Figure 3-8 Task description for multi-parameter request (example)