Communication according to PROFIdrive
3.5 Diagnostics channels
Communication
74 Function Manual, 12/2018, 6SL3097-5BD00-0BP0
3.5.2.5 Data sets DS0/DS1 and diagnostics alarm
The PROFIdrive message classes are transferred using diagnostic alarm DS0/DS1. All faults
are assigned channel 0. The drive objects are assigned using the slot number.
The structure is as follows:
1 Header-Byte 0 0 = 15 (block length)
0 ... 244 (slot number ≙ drive object)
0 ... 31 (sequence number)
1)
2)
3)
4)
5)
6)
6)
6)
6)
= 0x45 (ChannelTypeID = SINAMICS)
= 24 (number of diagnostic bits/channel)
12 Channel Error
Vector
0 0 0 0 0 0 0 Channel 0
Channel
-related diag-
nostics
15 0 0 0 0 Err 19 Err 18 Err 17 Err 16
Alarm_Specifier
1 ≙ error has occurred and the slot is not OK
2 ≙ error is resolved and the slot is OK
3 ≙ error is resolved and the slot is not okay
Channel fault present
= 1; as long as the drive object has an error condition
Internal fault
= 1; as long as the drive object has an error condition
Module fault
= 1; as long as the drive object has an error condition
Channel information present
= 1; ≙ DS1 exists
Type class of module