Communication via PROFINET IO
5.6 Communication via PROFINET Gate
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
137
5.6.1 Functions supported by PN Gate
PN Gate function overview
Function
Description
Communication channels
Cyclic data communication:
IRT
RT
Acyclic data communication:
- PROFINET alarms
- Read/write data set
- TCP/IP
PROFINET basic services
LLDP
DCP
SNMP
Accesses to process data Access to the process image:
Subslot granular
Device granular
Consistency of the cyclic data Each process data communication cycle can contain a data
component for IRT and RT communication
Network topologies
Line
Star
Tree
Information from the PN Gate
Device number
Slot number with the associated subslot numbers
IO address
Diagnostic addresses
Module ID (vendor ID and module ID)
Send cycles and update times
Activating/deactivating Activating and deactivating devices via the API without alarm
triggering
Automatic address assignment
Topology-based initialization
Number of IO devices
A maximum of 64 devices
IO area in the controller
4096 bytes each, in and out
Maximum number of slots: 2048
Maximum bytes per slot/module size: 254 bytes
Send cycle
RT communication: 1 ms
Update times RT 2
n
with n = 0 to 9x send cycle
IRT communication
1 ms - 4 ms in increments of 250 μs minimum send cycle of
1 ms for 32 devices. It is permissible to reduce the data per
device.