Communication via SINAMICS Link
8.3 Configuring and commissioning
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
207
8.3 Configuring and commissioning
Commissioning
When commissioning, proceed as follows:
1. Set the Control Unit parameter p0009 = 1 (device configuration).
2. Set the Control Unit parameter p8835 = 3 (SINAMICS Link).
3. Using p8839, define which interface should be used (for example for IF1: p8839[0] = 2).
4. If SINAMICS Link is assigned to IF1, set parameter p2037 of the drive objects to 2 (do not
freeze setpoints).
If SINAMICS Link was assigned IF2, then p8837 must be used for the setting.
5. Assign the nodes in parameter p8836 to the SINAMICS Link node number.
The first Control Unit is always assigned the number 1. Node number 0 means that for
this Control Unit SINAMICS Link has been shut down. Observe the specifications under
"Topology".
6. Check and/or correct the following parameters:
p8811 must be identical for all nodes
p8812[1] must be identical for all nodes
p8812[0] may be different for local nodes
7. Set the Control Unit parameter p0009 = 0 (ready).
8. Execute a "Copy RAM to ROM".
9. Carry out a POWER ON (switch off the Control Unit and switch on again).