Communication via PROFINET IO
5.9 PROFINET system redundancy
Communication
152 Function Manual, 12/2018, 6SL3097-5BD00-0BP0
5.9 PROFINET system redundancy
5.9.1 Overview
Thanks to SINAMICS S120 PROFINET Control Unit, the assembly of system-redundant
systems is possible.
Precondition for system-redundant systems is a so-called H-system. The H-system consists
of 2 fault-tolerant controls master and reserve CPU which are constantly synchronized
via fiber-optic cables. If one controller fails, the other automatically takes on the job. This
reduces system downtimes.
Requirements
SIMATIC controller S7-400H with two PROFINET H-CPUs type 41xH (or newer: e.g.
SIMATIC S7-1500 R/H)
SINAMICS S120 PROFINET Control Unit (CU310-2 PN or CU320-2 PN)
Redundant communication links
Benefits
No system downtime in the case of a controller failure
Component replacement possible during ongoing operation
Configuration changes possible during ongoing operation
Automatic synchronization after replacing components
Restrictions
IRT is not supported
No simultaneous operation of Shared Device and Shared I-Device
Maximum 2 cyclical PROFINET connections
System redundancy only via the onboard interface of SINAMICS S120 PROFINET
Control Unit
For the duration of switching from one controller to the other, the setpoints of the last
connection remain frozen and valid.