Communication via Ethernet/IP (EIP)
7.8 Messages and parameters
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
201
Integrating the drive into the EIP network via the X1400 interface at the CBE20
Integrating the drive into the EIP network via interface X1400 at the CBE20
1. Set p8944 (CBE2x DHCP mode) = 2 or 3.
The DHCP server assigns the IP address based on the MAC address.
p8944 = 3 The DHCP server assigns the IP address based on the station name.
2. Save the settings with p8945 = 2.
The next time that it is run-up, the drive retrieves the IP address made available by a
DHCP server. After the drive has run-up, you can address the drive as Ethernet
participant.
Note
Immediate switchover without restart
The switchover to DHCP is performed immediately and without a restart if the change is
carried out with the EIP command "Set Attribute Single" (class F5 hex, attribute 3), e.g.
using:
An EIP control
An EIP commissioning tool
Result:
You have integrated the drive into the EIP network via DHCP.
Displays
● r8950: Station name of interface X1400 at the CBE20
● r8954: DHCP mode of interface X1400 at the CBE20
● r8955: MAC address of interface X1400 at the CBE20
7.8 Messages and parameters
Faults and alarms (see SINAMICS S120/S150 List Manual)
F08501 (N,A)
PN/COMM BOARD: Setpoint timeout
F01910 (N,A)
Fieldbus: Setpoint timeout
A08526 (F)
PN/COMM BOARD: No cyclic connection
A01980 (F)
PN: Cyclic connection interrupted
A50011 (F)
EtherNetIP/COMM BOARD: Configuration error
A01906 (F)
EtherNet/IP Configuration error