Communication according to PROFIdrive
3.4 Acyclic communication
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
51
Overview of important parameters (see SINAMICS S120/S150 List Manual)
p0922
rive PZD telegram selection
p0978[0...n]
p8815[0...1]
IF1/IF2 PZD functionality selection
p8839[0...1]
PZD interface hardware assignment
3.4 Acyclic communication
3.4.1 General information about acyclic communication
With acyclic communication, as opposed to cyclic communication, data transfer takes place
only when an explicit request is made (e.g. in order to read and write parameters).
The "Read data record" and "Write data record" services are available for acyclic
communication.