Communication via PROFINET IO
5.10 PROFIenergy
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
159
Get_Measurement_Values Returns the requested measured value using the measured
value ID:
• For power measured values:
The command addresses the sum of the measured value
over all control drive objects.
• For energy measured values:
The command returns the sum of the measured value over
all control drive objects.
• For power factors:
This measured value is supported only for a SINAMICS
with a control drive object.
Get_Measurement_Values_with_obj
ect_number
Returns the requested measured values using the measured
value ID and the object number. The object number corre-
sponds to the drive object ID.
The drive object ID of the Control Unit is used to address the
measured values as with "Get_Measurement_Value".
5.10.3 PROFIenergy measured values
Table 5- 6 Overview of the PROFIenergy measured values
PROFIenergy measured
value
SINAMICS source parameters
34 Active power 1 12 W r0032 Active power
smoothed
Largest value for
r2004 of all drive
166 Power factor 1 12 1 r0038 Smoothed pow-
0 ... 1
200 Active energy
2 11 Wh r0039[1] Energy accept-
-