Communication via Modbus TCP
6.1 Overview
Communication
166 Function Manual, 12/2018, 6SL3097-5BD00-0BP0
General information about communication
Communication with Modbus TCP is established via the Ethernet/PROFINET interfaces:
X150
For Modbus TCP with a CU320-2 PN or CU310-2 PN.
X1400
For Modbus TCP with a CU320-2 PN or a CU320-2 DP via a CBE20.
Precisely one Modbus connection can be established. A simultaneous connection via the
interfaces X150 and X1400 is not possible and is acknowledged with alarm A08555(1).
However, you can use one interface for Modbus TCP, and the other as PROFINET interface.
Drive object that can be addressed via Modbus
With Modbus TCP, you always address the first control-drive object from the list of drive
objects (p0978[0]). A servo or vector drive object must be in this parameter.
However, Modbus TCP is only activated if, under p0978[0], there is a drive object that is
supported by Modbus TCP.
If p0978[0] does not contain a valid drive object, then establishing communication is
acknowledged with alarm A08555(2).
Diagnostics LEDs in Modbus TCP
Diagnostics states are shown as follows using LEDs with Modbus TCP:
X150: "
PN" LED
X1400 (CBE20): "
OPT" LED
The following states can be displayed by these LEDs:
Color
State
Meaning
Green Continuous
light
Connections and setpoints are OK.
Green Flashing light Connection is OK, but no setpoints (dependent on timeout).
Red Flashing light
2 Hz
No connection or setpoint timeout.