Communication via Modbus TCP
6.4 Mapping tables
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
171
ON/OFF text
or Value range
40513 Integral time of the technology control-
R/W s 1 0 … 60 p2285
40514 Time constant D-component of the
technology controller
R/W - 1 0 … 60 p2274
Max. limit of technology controller
Min. limit technology controller
40520 Effective setpoint acc. to internal tech-
nology controller MOP ramp-function
R % 100 -100.0 … 100.0 r2250
40521 Actual value of technology controller
R % 100 -100.0 … 100.0 r2266
Output signal technology controller
For these registers, for S120 servo drives, parameters p1120 and p1121 are only available (and can only be parameter-
ized) with the extended setpoint channel.
These registers are not supported for linear motors as the unit and value range differ from normal rotary drives.
You can only access the technology controller parameters if the "Technology controller" function module is also activat-
Table 6- 3 Assignment of the Modbus register for general parameter access using DS47
ON/OFF text
or Value range
Note
Limited value range
Modbus TCP registers have a maximum 16 bit width. The values of display parameters (r
parameters) cannot always be represented with 16 bits. In the
se particular cases, the
maximum value that can be represented is displayed.
Unsigned: 65535
Signed min: -32768
Signed max: 32767