Communication via PROFIBUS DP
4.2 Commissioning PROFIBUS
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
91
Field
Value
DBB, DBW, DBD
(data block offset)
Drive object No. and sub-index
bit 15 ... 10: Drive object No. 0 ... 63
bit 9 ... 0: Sub-index 0 ... 1023
or expressed differently
DBW = 1024 * drive object No. + sub-index
Length Not activated
Acquisition cycle
Any
Number of elements
1
Decimal places
Any
Note
You can operate a SIMATIC HMI together with a drive unit independently of an existing
controller.
A basic "point-to-point" connection can only be established between two nodes (devices).
The "variable" HMI function can be used for drive units. Other functions cannot be used
(e.g. "messages" or "recipes").
Individual parameter values can be accessed. Entire arrays, descriptions, or texts cannot
be accessed.