Communication via PROFIBUS
Acyclic communication
4-129
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Table 4-17 Error values in DPV1 parameter responses, continued
Error
value
Add.
informa-
tion
CommentsMeaning
0x78 Parameter %s [%s]: write access
only in the commissioning state,
drive configuration
(device: p0009 = 3).
- -
0x79 Parameter %s [%s]: write access
only in the commissioning state,
definition of the drive type
(device: p0009 = 2).
- -
0x7A Parameter %s [%s]: write access
only in the commissioning state,
data set basis configuration
(device: p0009 = 4).
- -
0x7B Parameter %s [%s]: write access
only in the commissioning state,
device configuration
(device: p0009 = 1).
- -
0x7C Parameter %s [%s]: write access
only in the commissioning state,
device download
(device: p0009 = 29).
- -
0x7D Parameter %s [%s]: write access
only in the commissioning state,
device parameter reset
(device: p0009 = 30).
- -
0x7E Parameter %s [%s]: write access
only in the commissioning state,
device ready (device: p0009 = 0).
- -
0x7F Parameter %s [%s]: write access
only in the commissioning state,
device (device: p0009 not equal
to 0).
- -
0x81 Parameter %s [%s] may not be
written in download.
- -
0x82 Transfer of the control authority
(master) is inhibited by BI: p0806.
- -
0x83 Parameter %s [%s]: Requested
BICO interconnection not possible
BICO output does not supply float values. The
BICO input, however, requires a float value.
-
0x84 Parameter %s [%s]: Free BICO
interconnection inhibited by
p0717.
- -
0x85 Parameter %s [%s]: Access
method not defined.
- -
0xC8 Below the valid values. Modification request for a value that, although
within “absolute” limits, is below the currently
valid lower limit.
-