EasyManua.ls Logo

Siemens SINAMICS S120 - Page 204

Siemens SINAMICS S120
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Diagnosis
Diagnostics using STARTER
6-204
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Note
Please refer to the online help for more information about parameterizing and
using the measuring sockets.
Properties
S Concurrent injection to several drives possible.
S The following parameterizable signal shapes can be set:
Square-wave
Staircase
Triangular
PRBS (pseudo random binary signal, white noise)
Sinusoidal
S An offset is possible for each signal. The ramp-up to the offset is
parameterizable. Signal generation begins after the ramp-up to the offset.
S Restriction of the output signal to the minimum and maximum value settable.
S Operating modes of the ramp-function generator for servo and vector
Connector output
S Operating modes of the ramp-function generator (servo only)
Current setpoint downstream of filter (current setpoint filter)
Disturbing torque (downstream of current setpoint filter)
Speed setpoint downstream of filter (speed setpoint filter)
Current setpoint upstream of filter (current setpoint filter)
Speed setpoint upstream of filter (speed setpoint filter)
Injection points of the ramp-function generator
funk_gen_ueber.vsd
From
interpolator
Setpoint
filter
Speed
controller
Setpoint
filter
Power
controller
Controlled
Speed setpoint
upstream of filter
Speed setpoint
downstream of filter
Disturbing torque
Current setpoint
upstream of filter
Current setpoint
downstream of filter
system
Fig. 6-3 Injection points of the ramp-function generator

Table of Contents

Other manuals for Siemens SINAMICS S120

Related product manuals