Basic Information about the Drive System
Inputs/outputs
7-258
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Bidirectional digital inputs/outputs
+
digital_in_out_bi.vsd
DI
DO
+24V
X124.1
DI/DO 0X122.7
0
1
p0728.8
X122.12
X122.9
M
M
5 V
24 V
r0747.8
r0747
X124.4
M
X124.3
M
p0727.0
p0721.0
0
1
1
r0723.0
r0722.0
p4030 (0)
p4048.0
1
0
1
Fig. 7-12 Bidirectional inputs/outputs: signal: processing using DI/DO 0 of CU320 as an example
Properties
S Can be parameterized as digital input or output.
S When set as digital input:
– Six “high-speed inputs” on Control Unit 320
If these inputs are used, for example, for the “measurement on-the-fly”
function, they act as “high-speed inputs” with virtually no time delay when
the actual value is saved.
– The properties of the “pure” digital inputs apply.
S When set as digital output:
– The properties of the “pure” digital outputs apply.
Function diagram overview (see List Manual)
S 2130 Digital inputs/outputs bidirec. (DI/DO 8 and DI/DO 9)
S 2131 Digital inputs/outputs bidirec. (DI/DO 10 and DI/DO 11)
S 2132 Digital inputs/outputs bidirec. (DI/DO 12 and DI/DO 13)
S 2133 Digital inputs/outputs bidirec. (DI/DO 14 and DI/DO 15)
S 9560 Digital inputs/outputs bidirec. (DI/DO 8 and DI/DO 9)
S 9562 Digital inputs/outputs bidirec. (DI/DO 10 and DI/DO 11)