Commissioning
Initial commissioning using vector (chassis) as an example
3-74
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Table 3-9 Commissioning sequence with STARTER (example), continued
What to do? CommentsHow to do it?
5. Save the
parameters
on the device
S Connect with target system (go online)
S Target system –> Load to target system
S Target system –> Copy from RAM to ROM
Position cursor on drive unit
(SINAMICS S120) and
right-click.
6. The motor
starts
rotating.
The drives can be started via the control panel in
STARTER.
S This can be done once the pulses have been
enabled for the infeed and line/DC link
identification has been activated. The infeed
then switches to operational mode.
S When the pulses are enabled, a one-off motor
data identification run (if activated) is carried out.
S When the pulses are enabled again,
optimization with a rotating motor (if activated) is
carried out.
For more information about
the control panel, see Getting
Started.
During motor identification, a
current flows through the
motor, which means that it
can align itself by up to a
quarter of a revolution.
For more information about
line/DC link identification and
motor identification, see the
Function Manual.
Parameter overview for diagnosis (see List Manual)
r0002 Infeed/drive operating display
r0046 Missing enable signals (see Diagnostics chapter for further
information)
J