Commissioning
Initial commissioning using vector (chassis) as an example
3-73
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Table 3-9 Commissioning sequence with STARTER (example), continued
What to do? CommentsHow to do it?
4.5. Motor
temperature
Temperature sensor selection: via Motor Module
(11)
Temperature sensor type: KTY84 (2)
Response to overtemperature: Alarm and fault (no
reduction of Imax)
Fault message for thermistor failure: ON
Delay time: 0.100 s
Alarm threshold: 120.0 °C
Fault threshold: 155.0 °C