Functions
6-1057SA522 Manual
C53000-G1176-C119-2
For the inverse time overcurrent stage 3I
0P
it is possible to select from a variety of
curves depending on the version of the relay and the configuration (Section 5.1, ad-
dress ) that was selected. If an inverse overcurrent stage is not required, the ad-
dress LVVHWWR(DUWK)DXOW2& = 'HILQLWH7LPH. The 3I
0P
–stage
can then be used as a fourth definite time stage (refer to “Definite Time Stages”
above). In the case of the ANSI–curves (address  (DUWK)DXOW2& = 72&
$16,) the following alternatives are available in the address  $16,&XUYH:
,QYHUVH,
6KRUWLQYHUVH,
/RQJLQYHUVH,
0RGHUDWHO\LQY,
9HU\LQYHUVH,
([WUHPHO\LQY and
'HILQLWHLQY
The curves and equations the curves are based on are illustrated in the technical data
(Section 10.9).
The setting of the pick-up threshold ,S3,&.83 (address ) is similar to the
setting of definite time stages (see above). In this case it must be considered that a
safety margin has already been included between the pick-up threshold and the set-
ting value. The stage only picks up when the measured signal is approximately 10 %
above the setting value.
The time multiplier setting ,S7LPH'LDO (address ) is derived from the grad-
ing coordination chart which was set up for earth faults in the system.
In addition to the inverse current dependant time delay, a constant (fixed length) time
delay can also be set if this is required. The setting $GG7'(/$< (address ) is
added to the time of the set curve.
Inverse Time Over-
current Stage with
Logarithmic–
Inverse Character-
istic
For the inverse time overcurrent stage with logarithmic inverse characteristic the op-
erating mode is initially set: 2SPRGH,S (address ). This stage can be set
to operate
forward
(usually towards line) or
reverse direction
(usually towards bus-
bar) or
non-directional
(in both directions). If an individual stage is not required, set
its mode to
inactive
.
For the inverse logarithmic curves (address  (DUWK)DXOW2& = 72&/RJD
ULWKP) the following can be set: address  /2*&XUYH = /RJLQYHUVH
The curves and equations the curves are based on are illustrated in the technical data
(Section 10.5). Figure 6-63 illustrates the influence of the most important setting pa-
rameters on the curve. ,S3,&.83 (address ) is the reference value for all
current values, while ,S6WDUWSRLQW (address ) determines the beginning
of the curve, i.e. the lowest operating range on the current axis (referred to ,S
3,&.83). The timer setting ,S0D[7'(/$< (address ) determines the start-
ing point of the curve (for 3I
0
= ,S3,&.83). The time factor ,S7LPH'LDO
(address ) changes the slope of the curve. For large currents, ,S0LQ7'(
/$< (address ) determines the lower limit on the time axis. For currents larger
than 30·,S3,&.83the operating time no longer decreases.
Finally in address  $GG7'(/$< a fixed time delay can be set as was done for
other curves. This, however, has almost the same effect as an increase of ,S
0D[7'(/$< (address ).

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals