Appendix
B-6
1243 R load (Ø-Ø) Distance protec-
tion, general set-
tings
0.10..250.00 Ohm
1
; Ohm R load, minimum Load Impedance (ph-
ph)
1244 ϕ load (Ø-Ø) Distance protec-
tion, general set-
tings
20..60 ° 45 ° PHI load, maximum Load Angle (ph-
ph)
1301 Op. mode Z1 Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Forward Operating mode Z1
1302 R(Z1) Ø-Ø Distance zones
(quadrilateral)
0.05..250.00 Ohm 1.25 Ohm R(Z1), Resistance for ph-ph-faults
1303 X(Z1) Distance zones
(quadrilateral)
0.05..250.00 Ohm 2.50 Ohm X(Z1), Reactance
1304 RE(Z1) Ø-E Distance zones
(quadrilateral)
0.05..250.00 Ohm 2.50 Ohm RE(Z1), Resistance for ph-e faults
1305 T1-1phase Distance zones
(quadrilateral)
0.00..30.00 sec 0.00 sec T1-1phase, delay for single phase
faults
1305 T1-1phase Distance zones (
MHO)
0.00..30.00 sec 0.00 sec T1-1phase, delay for single phase
faults
1306 T1-multi-phase Distance protec-
tion, general set-
tings
0.00..30.00 sec 0.00 sec T1multi-ph, delay for multi phase faults
1306 T1-multi-phase Distance zones
(quadrilateral)
0.00..30.00 sec 0.00 sec T1multi-ph, delay for multi phase faults
1306 T1-multi-phase Distance zones (
MHO)
0.00..30.00 sec 0.00 sec T1multi-ph, delay for multi phase faults
1307 Zone Reduction Distance zones
(quadrilateral)
0..30 ° 0 ° Zone Reduction Angle (load compen-
sation)
1311 Op. mode Z2 Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Forward Operating mode Z2
1312 R(Z2) Ø-Ø Distance zones
(quadrilateral)
0.05..250.00 Ohm 2.50 Ohm R(Z2), Resistance for ph-ph-faults
1313 X(Z2) Distance zones
(quadrilateral)
0.05..250.00 Ohm 5.00 Ohm X(Z2), Reactance
1314 RE(Z2) Ø-E Distance zones
(quadrilateral)
0.05..250.00 Ohm 5.00 Ohm RE(Z2), Resistance for ph-e faults
1315 T2-1phase Distance zones
(quadrilateral)
0.00..30.00 sec 0.30 sec T2-1phase, delay for single phase
faults
1315 T2-1phase Distance zones (
MHO)
0.00..30.00 sec 0.30 sec T2-1phase, delay for single phase
faults
1316 T2-multi-phase Distance zones
(quadrilateral)
0.00..30.00 sec 0.30 sec T2multi-ph, delay for multi phase faults
1316 T2-multi-phase Distance zones (
MHO)
0.00..30.00 sec 0.30 sec T2multi-ph, delay for multi phase faults
1317 Trip 1pole Z2 Distance zones
(quadrilateral)
NO
YES
NO Single pole trip for faults in Z2
1317 Trip 1pole Z2 Distance zones (
MHO)
NO
YES
NO Single pole trip for faults in Z2
1321 Op. mode Z3 Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Reverse Operating mode Z3
1322 R(Z3) Ø-Ø Distance zones
(quadrilateral)
0.05..250.00 Ohm 5.00 Ohm R(Z3), Resistance for ph-ph-faults
1323 X(Z3) Distance zones
(quadrilateral)
0.05..250.00 Ohm 10.00 Ohm X(Z3), Reactance
Addr. Setting Title Function Setting Options Default Setting Comments