Appendix
B-7
7SA522 Manual
C53000-G1176-C119-2
1324 RE(Z3) Ø-E Distance zones
(quadrilateral)
0.05..250.00 Ohm 10.00 Ohm RE(Z3), Resistance for ph-e faults
1325 T3 DELAY Distance zones
(quadrilateral)
0.00..30.00 sec 0.60 sec T3 delay
1325 T3 DELAY Distance zones (
MHO)
0.00..30.00 sec 0.60 sec T3 delay
1331 Op. mode Z4 Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Non-Directional Operating mode Z4
1332 R(Z4) Ø-Ø Distance zones
(quadrilateral)
0.05..250.00 Ohm 12.00 Ohm R(Z4), Resistance for ph-ph-faults
1333 X(Z4) Distance zones
(quadrilateral)
0.05..250.00 Ohm 12.00 Ohm X(Z4), Reactance
1334 RE(Z4) Ø-E Distance zones
(quadrilateral)
0.05..250.00 Ohm 12.00 Ohm RE(Z4), Resistance for ph-e faults
1335 T4 DELAY Distance zones
(quadrilateral)
0.00..30.00 sec 0.90 sec T4 delay
1335 T4 DELAY Distance zones (
MHO)
0.00..30.00 sec 0.90 sec T4 delay
1341 Op. mode Z5 Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Inactive Operating mode Z5
1342 R(Z5) Ø-Ø Distance zones
(quadrilateral)
0.05..250.00 Ohm 12.00 Ohm R(Z5), Resistance for ph-ph-faults
1343 X(Z5)+ Distance zones
(quadrilateral)
0.05..250.00 Ohm 12.00 Ohm X(Z5)+, Reactance for Forward direc-
tion
1344 RE(Z5) Ø-E Distance zones
(quadrilateral)
0.05..250.00 Ohm 12.00 Ohm RE(Z5), Resistance for ph-e faults
1345 T5 DELAY Distance zones
(quadrilateral)
0.00..30.00 sec 0.90 sec T5 delay
1345 T5 DELAY Distance zones (
MHO)
0.00..30.00 sec 0.90 sec T5 delay
1346 X(Z5)- Distance zones
(quadrilateral)
0.05..250.00 Ohm 4.00 Ohm X(Z5)-, Reactance for Reverse direc-
tion
1351 Op. mode Z1B Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Forward Operating mode Z1B (overrreach
zone)
1352 R(Z1B) Ø-Ø Distance zones
(quadrilateral)
0.05..250.00 Ohm 1.50 Ohm R(Z1B), Resistance for ph-ph-faults
1353 X(Z1B) Distance zones
(quadrilateral)
0.05..250.00 Ohm 3.00 Ohm X(Z1B), Reactance
1354 RE(Z1B) Ø-E Distance zones
(quadrilateral)
0.05..250.00 Ohm 3.00 Ohm RE(Z1B), Resistance for ph-e faults
1355 T1B-1phase Distance zones
(quadrilateral)
0.00..30.00 sec 0.00 sec T1B-1phase, delay for single ph. faults
1355 T1B-1phase Distance zones (
MHO)
0.00..30.00 sec 0.00 sec T1B-1phase, delay for single ph. faults
1356 T1B-multi-phase Distance zones
(quadrilateral)
0.00..30.00 sec 0.00 sec T1B-multi-ph, delay for multi ph. faults
1356 T1B-multi-phase Distance zones (
MHO)
0.00..30.00 sec 0.00 sec T1B-multi-ph, delay for multi ph. faults
1357 1st AR -> Z1B Distance zones
(quadrilateral)
NO
YES
YES Z1B enabled before 1st AR (int. or ext.)
1357 1st AR -> Z1B Distance zones (
MHO)
NO
YES
YES Z1B enabled before 1st AR (int. or ext.)
Addr. Setting Title Function Setting Options Default Setting Comments