Appendix
B-43
7SA522 Manual
C53000-G1176-C119-2
6861 Trip circuit supervision OFF (TripC
OFF)
Trip Circuit
Supervision
OUT ON
OFF
* LED BO
6865 Failure Trip Circuit (FAIL: Trip cir.) Trip Circuit
Supervision
OUT ON
OFF
* LED BO
6866 TripC1 blocked: Binary input is not
set (TripC1 ProgFAIL)
Trip Circuit
Supervision
OUT ON
OFF
* LED BO
6867 TripC2 blocked: Binary input is not
set (TripC2 ProgFAIL)
Trip Circuit
Supervision
OUT ON
OFF
* LED BO
6868 TripC3 blocked: Binary input is not
set (TripC3 ProgFAIL)
Trip Circuit
Supervision
OUT ON
OFF
* LED BO
7104 >BLOCK Backup OverCurrent I>>
(>BLOCK O/C I>>)
Backup over-
current
SP ON
OFF
* LED BI BO 64 4 1 GI
7105 >BLOCK Backup OverCurrent I>
(>BLOCK O/C I>)
Backup over-
current
SP ON
OFF
* LED BI BO 64 5 1 GI
7106 >BLOCK Backup OverCurrent Ip
(>BLOCK O/C Ip)
Backup over-
current
SP ON
OFF
* LED BI BO 64 6 1 GI
7110 >Backup OverCurrent Instanta-
neousTrip (>O/C InstTRIP)
Backup over-
current
SP ON
OFF
ON
OFF
LED BI BO 64 10 1 GI
7130 >BLOCK I-STUB (>BLOCK I-STUB) Backup over-
current
SP ON
OFF
* LED BI BO 64 30 1 GI
7131 >Enable I-STUB-Bus function (>I-
STUB ENABLE)
Backup over-
current
SP ON
OFF
ON
OFF
LED BI BO 64 31 1 GI
7151 Backup O/C is switched OFF (O/C
OFF)
Backup over-
current
OUT ON
OFF
* LED BO 64 51 1 GI
7152 Backup O/C is BLOCKED (O/C
BLOCK)
Backup over-
current
OUT ON
OFF
ON
OFF
LED BO 64 52 1 GI
7153 Backup O/C is ACTIVE (O/C
ACTIVE)
Backup over-
current
OUT * * LED BO 64 53 1 GI
7161 Backup O/C PICKED UP (O/C
PIKKUP)
Backup over-
current
OUT *
OFF
M LED BO 64 61 2 GI
7162 Backup O/C PICKUP L1 (O/C Pickup
L1)
Backup over-
current
OUT * ON LED BO 64 62 2 GI
7163 Backup O/C PICKUP L2 (O/C Pickup
L2)
Backup over-
current
OUT * ON LED BO 64 63 2 GI
7164 Backup O/C PICKUP L3 (O/C Pickup
L3)
Backup over-
current
OUT * ON LED BO 64 64 2 GI
7165 Backup O/C PICKUP EARTH (O/C
Pickup E)
Backup over-
current
OUT * ON LED BO 64 65 2 GI
7171 Backup O/C Pickup - Only EARTH
(O/C PU only E)
Backup over-
current
OUT * ON LED BO 64 71 2
7172 Backup O/C Pickup - Only L1 (O/C
PU 1p. L1)
Backup over-
current
OUT * ON LED BO 64 72 2
7173 Backup O/C Pickup L1E (O/C Pickup
L1E)
Backup over-
current
OUT * ON LED BO 64 73 2
7174 Backup O/C Pickup - Only L2 (O/C
PU 1p. L2)
Backup over-
current
OUT * ON LED BO 64 74 2
7175 Backup O/C Pickup L2E (O/C Pickup
L2E)
Backup over-
current
OUT * ON LED BO 64 75 2
F.No. Description Function Type of Infor-
mation
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation