Appendix
B-26
7SA6 Manual
C53000-G1176-C156-2
353 >Circuit breaker aux. contact: Pole L3
(>CB Aux. L3)
Power System
Data 2
SP * * LED BI BO 150 3 1 GI
356 >Manual close signal (>Manual Close) Power System
Data 2
SP * * LED BI BO 150 6 1 GI
357 >Block all Close commands from external
(>Close Cmd. Blk)
Power System
Data 2
SP ON
OFF
* LED BI BO 150 7 1 GI
361 >Failure: Feeder VT (MCB tripped)
(>FAIL:Feeder VT)
Power System
Data 2
SP ON
OFF
* LED BI BO 128 38 1 GI
362 >Failure: Busbar VT (MCB tripped)
(>FAIL:Bus VT)
Power System
Data 2
SP ON
OFF
* LED BI BO 150 12 1 GI
366 >CB1 Pole L1 (for AR,CB-Test) (>CB1
Pole L1)
Power System
Data 2
SP * * LED BI BO 150 66 1 GI
367 >CB1 Pole L2 (for AR,CB-Test) (>CB1
Pole L2)
Power System
Data 2
SP * * LED BI BO 150 67 1 GI
368 >CB1 Pole L3 (for AR,CB-Test) (>CB1
Pole L3)
Power System
Data 2
SP * * LED BI BO 150 68 1 GI
371 >CB1 READY (for AR,CB-Test) (>CB1
Ready)
Power System
Data 2
SP * * LED BI BO 150 71 1 GI
378 >CB faulty (>CB faulty) Power System
Data 2
SP * * LED BI BO
379 >CB aux. contact 3pole Closed (>CB 3p
Closed)
Power System
Data 2
SP * * LED BI BO 150 78 1 GI
380 >CB aux. contact 3pole Open (>CB 3p
Open)
Power System
Data 2
SP * * LED BI BO 150 79 1 GI
381 >Single-phase trip permitted from ext.AR
(>1p Trip Perm)
Power System
Data 2
SP ON
OFF
* LED BI BO
382 >External AR programmed for 1phase
only (>Only 1ph AR)
Power System
Data 2
SP ON
OFF
* LED BI BO
383 >Enable all AR Zones / Stages (>Enable
ARzones)
Power System
Data 2
SP ON
OFF
ON
OFF
LED BI BO
385 >Lockout SET (>Lockout SET) Power System
Data 2
SP ON
OFF
* LED BI BO 150 35 1 GI
386 >Lockout RESET (>Lockout RESET) Power System
Data 2
SP ON
OFF
* LED BI BO 150 36 1 GI
395 >I MIN/MAX Buffer Reset (>I MinMax
Reset)
Min/Max Mea-
surement Setup
SP ON * LED BI BO
396 >I1 MIN/MAX Buffer Reset (>I1 MiMaRe-
set)
Min/Max Mea-
surement Setup
SP ON * LED BI BO
397 >U MIN/MAX Buffer Reset (>U MiMaRe-
set)
Min/Max Mea-
surement Setup
SP ON * LED BI BO
398 >Uphph MIN/MAX Buffer Reset (>Uphph-
MiMaRes)
Min/Max Mea-
surement Setup
SP ON * LED BI BO
399 >U1 MIN/MAX Buffer Reset (>U1 MiMa
Reset)
Min/Max Mea-
surement Setup
SP ON * LED BI BO
400 >P MIN/MAX Buffer Reset (>P MiMa
Reset)
Min/Max Mea-
surement Setup
SP ON * LED BI BO
401 >S MIN/MAX Buffer Reset (>S MiMa
Reset)
Min/Max Mea-
surement Setup
SP ON * LED BI BO
F.No. Description Function Type of
Informa-
tion
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation