Appendix
B-55
7SA6 Manual
C53000-G1176-C156-2
10258 Uph-ph>(>) Pickup L2-L3 (Uphph>(>)PU
L23)
VoltageProtection OUT * ON
OFF
LED BO 73 58 2 GI
10259 Uph-ph>(>) Pickup L3-L1 (Uphph>(>)PU
L31)
VoltageProtection OUT * ON
OFF
LED BO 73 59 2 GI
10260 Uph-ph> TimeOut (Uphph> TimeOut) Voltage Protection OUT * * LED BO
10261 Uph-ph>> TimeOut (Uphph>> TimeOut) Voltage Protection OUT * * LED BO
10262 Uph-ph>(>) TRIP command (Uphph>(>)
TRIP)
VoltageProtection OUT * ON LED BO 73 62 2 GI
10270 3U0> Pickup (3U0> Pickup) Voltage Protection OUT * ON
OFF
LED BO 73 70 2 GI
10271 3U0>> Pickup (3U0>> Pickup) Voltage Protection OUT * ON
OFF
LED BO 73 71 2 GI
10272 3U0> TimeOut (3U0> TimeOut) Voltage Protection OUT * * LED BO
10273 3U0>> TimeOut (3U0>> TimeOut) Voltage Protection OUT * * LED BO
10274 3U0>(>) TRIP command (3U0>(>) TRIP) Voltage Protection OUT * ON LED BO 73 74 2 GI
10280 U1> Pickup (U1> Pickup) Voltage Protection OUT * ON
OFF
LED BO 73 80 2 GI
10281 U1>> Pickup (U1>> Pickup) Voltage Protection OUT * ON
OFF
LED BO 73 81 2 GI
10282 U1> TimeOut (U1> TimeOut) Voltage Protection OUT * * LED BO
10283 U1>> TimeOut (U1>> TimeOut) VoltageProtection OUT * * LED BO
10284 U1>(>) TRIP command (U1>(>) TRIP) Voltage Protection OUT * ON LED BO 73 84 2 GI
10290 U2> Pickup (U2> Pickup) Voltage Protection OUT * ON
OFF
LED BO 73 90 2 GI
10291 U2>> Pickup (U2>> Pickup) Voltage Protection OUT * ON
OFF
LED BO 73 91 2 GI
10292 U2> TimeOut (U2> TimeOut) Voltage Protection OUT * * LED BO
10293 U2>> TimeOut (U2>> TimeOut) VoltageProtection OUT * * LED BO
10294 U2>(>) TRIP command (U2>(>) TRIP) Voltage Protection OUT * ON LED BO 73 94 2 GI
10300 U1< Pickup (U1< Pickup) Voltage Protection OUT * ON
OFF
LED BO 73 100 2 GI
10301 U1<< Pickup (U1<< Pickup) Voltage Protection OUT * ON
OFF
LED BO 73 101 2 GI
10302 U1< TimeOut (U1< TimeOut) Voltage Protection OUT * * LED BO
10303 U1<< TimeOut (U1<< TimeOut) VoltageProtection OUT * * LED BO
10304 U1<(<) TRIP command (U1<(<) TRIP) Voltage Protection OUT * ON LED BO 73 104 2 GI
10310 Uph-e< Pickup (Uph-e< Pickup) Voltage Protection OUT * ON
OFF
LED BO 73 110 2 GI
10311 Uph-e<< Pickup (Uph-e<< Pickup) Voltage Protection OUT * ON
OFF
LED BO 73 111 2 GI
10312 Uph-e<(<) Pickup L1 (Uph-e<(<) PU L1) Voltage Protection OUT * ON
OFF
LED BO 73 112 2 GI
10313 Uph-e<(<) Pickup L2 (Uph-e<(<) PU L2) Voltage Protection OUT * ON
OFF
LED BO 73 113 2 GI
F.No. Description Function Type of
Informa-
tion
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation