Introduction
6
7SS52 V4 Manual
C53000-G1176-C182-3
• Output of indications to
− Control center
− LEDs
− Binary outputs of the central unit
• Commissioning support by measuring and display functions, and output of indica-
tions to a control center as well as to LEDs and outputs of the central unit.
Busbar
protection
The digital busbar protection contains the following functions:
• Evaluation of the differential current in conjunction with through-current stabilization
(Figure 1-2, page 7)
• Trip decision based on 3 independent measurements. 2 measurements are based
on busbar configuration, and the third measurement considers all busbar sections
independent of the isolator replica (check zone).
• Fast tripping (typical trip time 15 ms)
• Busbar protection with up to 12 bus zones (BZ), 12 bus coupler (auxiliary bus) sec-
tions (AB) and up to 48 bay units
• Protection of systems with up to quintuple busbars (including transfer busbars)
• Stabilization against spurious tripping in case of external faults and CT saturation
• Zone-selective and phase-selective blocking of the busbar protection by the differ-
ential current monitor
• Selective blocking of the bus section in case of
− Isolator faults
− Bay faults (bay unit, FO cable)
− Measured value error
− Response of the zero crossing supervision
• Characteristics for check zone and bus-selective zones can be set independently
from each other
− Normal pick-up characteristic (Figure 1-2, page 7)
− Earth fault characteristic (Figure 1-3, page 7)
• Matching to different CT ratios without interposing matching transformers
• Selective clearance of short-circuits even on the bypass bus with signal transmis-
sion to the remote end
• Detection and disconnection of short-circuits in the coupler bay between current
transformers and circuit-breaker based on current measurement and selective un-
balance
• Detection and disconnection of short-circuits between current transformers and cir-
cuit-breaker of a line by end fault protection
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS523 V3.2 and is the answer not in the manual?

Siemens SIPROTEC 7SS523 V3.2 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS523 V3.2
CategoryPower distribution unit
LanguageEnglish

Related product manuals