Introduction
8
7SS52 V4 Manual
C53000-G1176-C182-3
Breaker failure
protection
The integrated circuit breaker failure protection (CBF) contains the following functions:
• In case of a busbar short-circuit, a breaker failure is detected by comparison of cur-
rent thresholds.
• In all operating modes of the circuit breaker failure protection, a bay-selective com-
mand is output by the bay units to trip the circuit breaker at the remote end (transfer
trip command).
• The external breaker failure protection can be started for one phase or for three
phases.
• The breaker failure protection can be started on 1 channel or, for extra reliability, on
2 channels. Both settings can be combined with a monitoring feature.
• Reduced response times in case of a circuit breaker malfunction
• Query of the circuit breaker position in case of low-current faults
• The circuit breaker failure protection function can be deactivated for test purposes.
The following modes are available for the circuit breaker failure protection:
• I> query:
After initiation by a TRIP command from the feeder protection, the 7SS52 V4
checks the feeder current. If the measured current stays above the set threshold af-
ter a set time has elapsed, the 7SS52 V4 issues zone-selective TRIP commands in
the bays considering the isolator replica.
• TRIP repetition with subsequent I> query:
When initiated by a TRIP command from the feeder protection, the 7SS52 V4 is-
sues a second TRIP command to the circuit breaker of the initiating feeder after a
set time delay. In case this second TRIP command is also unsuccessful, tripping as
per mode I>query is effected.
• Unbalancing:
After initiation by a TRIP command from the feeder protection, the
7SS52 V4 system checks the feeder current. If the measured current stays above
the set threshold after a set time has elapsed, the polarity of the current in this feed-
er is inverted by the 7SS52 V4 (unbalancing).
• TRIP repetition with subsequent unbalancing:
When initiated by a TRIP command from the feeder protection, the 7SS52 V4 is-
sues a second TRIP command to the circuit breaker of the initiating feeder after a
set time delay. In case this second TRIP command is also unsuccessful, tripping as
per mode Unbalancing is effected.
• TRIP by external CBF:
Where a separate circuit breaker failure protection is provided, the 7SS52 V4 can
generate zone-selective feeder trip commands utilizing the integrated isolator rep-
lica.
• TRIP repetition with subsequent unbalancing with pulse trigger or I>query:
This mode should be used when the CBF is triggered by the remote station. The
function is triggered by a trip command from the feeder protection at the remote
feeder terminal. The further proceeding is described in the modes TRIP repetition
with subsequent unbalancing and I>query.
• Low-current CBF:
This mode outputs a TRIP command even in the case of low-current faults (e.g. trip-
ping by Buchholz protection). After a settable time the circuit breaker position is
queried. A TRIP repetition also takes place with a low-current operating mode.
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS523 V3.2 and is the answer not in the manual?

Siemens SIPROTEC 7SS523 V3.2 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS523 V3.2
CategoryPower distribution unit
LanguageEnglish

Related product manuals