Functions
8.11 Standard 3RW5 HMI
SIRIUS 3RW52 Soft Starter
152 Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
Display
Explanation
CNTRL (CONTROL)
LOCL
CNTRL
Manual mode The master control function is with the 3RW5 HMI Standard
("Manual operation local - HMI controlled" mode).
REMT
CNTRL
Automatic Master control function is not with the 3RW5 HMI Standard.
To make the unit the master control, press the LOCL/REMT
key. Refer to chapter Operating modes and master control
function (Page 32).
Measured values
Display
Explanation
...A
I AVG
The average of the 3 phase currents is displayed in amps.
...A
I L1
Current measured value phase L1 is displayed in amps.
...A
I L2
Current measured value phase L2 is displayed in amps.
...A
I L3
Current measured value phase L3 is displayed in amps.
Parameter list
Display
Explanation
..
xIe
Current limiting value as a multiple of the set rated operational current I
e
of the
motor.
...%
U ON
Starting voltage
...s
t ON
Ramp up time
...s
t OFF
Stopping time
...
CLASS
Trip class for motor overload protection
...A
Ie
Rated operational current I
e
of the motor
....
RMode
AUTO
Auto RESET
MAN
Manual RESET
REMT
Remote RESET
...
PBADR
Station address for PROFIBUS
(only displayed if a 3RW5 PROFIBUS communication module is used)
...
MODBS
Station address for Modbus
(only displayed if a 3RW5 Modbus RTU communication module is used)