Functions
8.11 Standard 3RW5 HMI
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
153
Diagnostics display
Display
Explanation
....
ERROR
Standard 3RW5 HMI menu (Page 151)
Faults and remedial actions of the 3RW52 soft starter (Page 176)
NO
COMM
No connection between the 3RW52 soft starter and the 3RW5 HMI Standard.
Display of the error number with 3RW5 HMI Standard
The 3RW5 HMI Standard can display up to 10 active errors (ER 0 ... 9) in the menu item
"ERROR".
Procedure
1. Select the menu item "ERROR".
2. Press and hold a navigation key until the entry "ER 0" appears on the display.
3. Select the desired entry (ER 0 ... 9) using the navigation key.
If an entry contains an active error, the associated error number (Page 176) will appear
above it.
If an entry contains no errors, the error number "0000" will appear.
4. To exit the menu, press and hold a navigation key until the entry "ERROR" appears on
the display.
Alternatively, the 3RW5 HMI Standard automatically exits the menu after 5 seconds of
inactivity.