A5E33329501 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS Page 33
mmmmm
Commissioning
Commissioning
Local Commissioning
SITRANS LUT400 is an easy to use, and quick to commission device, with its numerous
wizards, and menu driven parameters. The parameters can be modified locally using the
LCD and the local push buttons, also known as the Local User Interface (LUI).
A Quick Start Wizard provides an easy step-by-step procedure to help you configure the
device for a simple application. We recommend that you configure your application in the
following order:
First, run the appropriate Quick Start Wizard for your application (Level, Volume,
Flow).
Next, setup pumps via the Pump Control Wizard (if applicable).
Lastly, configure alarms, or other controls, totalizers and samplers, referencing the
respective parameters [see
Parameter reference (LUI)
on page 137]. It is important
that alarms, and other controls
are configured last to avoid pump relay assignments
being overridden by the Quick Start Wizard.
There are two ways to access the Quick Start wizards:
locally (see
Quick Start Wizards via LUI
on page 38)
from a remote location (see
Other Quick Start Wizards (QSW):
on page 38)
See
Level Application Example
on page 58, or
Flow application example
on page 59 for
illustrations, and for the complete range of parameters, see
Parameter reference (LUI)
on
page 137.
Activating SITRANS LUT400
Notes:
Program Mode and Measurement mode refer to the display only. While the device is
in Program mode, the output remains active and continues to respond to changes in
the device.
To enter Program mode using the device local push buttons, press . Press to
return to Measurement mode.
The display will return to Measurement mode after ten minutes of inactivity (from
last button press), when in Program Mode and from within a Wizard. Pressing will
then take you to the main navigation menu. (It will not return to the screen from
which the timeout occurred.)