A5E33329501 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS Page 57
mmmmm
Commissioning
Requesting an Echo Profile
• In PROGRAM mode, navigate to: Main Menu > Diagnostics (3.2.) > Echo Profile
(3.2.1.).
• Press RIGHT arrow to request a profile.
•Use UP or DOWN arrow to scroll to an icon. When an icon is highlighted,
that feature becomes active.
• To move a cross-hair, press RIGHT arrow to increase the value, LEFT arrow
to decrease.
• To Zoom into an area, position the intersection of the cross-hairs at the center of
that area, select Zoom, and press RIGHT arrow . Press LEFT arrow to Zoom
out.
• To update the profile, select Measure and press RIGHT arrow .
• To return to the previous menu, select Exit then press RIGHT arrow .
Device Address
Setting a device address is not necessary for local operation, but must be set if
configuring the SITRANS LUT400 for use on a HART network. See
Device Address 4.1.
on
page 217.
Testing the configuration
After programming the device, it is recommended that you test the device to ensure that it
performs to your specifications. This test can be run in simulation mode or by varying the
actual level in the application. The latter is preferred as it more accurately represents
running conditions. However, if it is not possible to do a physical test, a simulation will
ensure that control programming is correct. For further details, see
Simulation
on page
120, and
Application test
on page 123.
C: 38 A: BLF D: 9.00
DB
0 2.0 4.0 6.0
0
50
100
algorithm
2
: BLF (Best of First or Largest echo)
confidence
1
distance from transducer face to target
TVT
echo
measure
exit
zoom
pan left/right - selected
pan up/down
Echo amplitude (in dB)
1. See Confidence (3.2.9.2.) on page 204.
2. See Algorithm (2.12.2.1.) on page 182.