Page 56 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS 7ML1998MV01
mmmmm
Commissioning
ON Setpoint Pump 1
The level at which Pump 1 turns ON, defined in 2.1.1. Units.
ON Setpoint Pump 2
The level at which Pump 2 turns ON, defined in 2.1.1. Units.
OFF Setpoint Pump 1
The level at which Pump 1 turns OFF, defined in 2.1.1. Units.
OFF Setpoint Pump 2
The level at which Pump 2 turns OFF, defined in 2.1.1. Units.
End of Wizard - Pump Control
For Wizard to be successful, all changes must be applied.
To transfer values to the device and return to Program menu, press DOWN arrow
(Finish). Then press LEFT arrow two times to return to Measurement mode.
Value
Range: 0.000 to 99999.000
Default: 0.000
Value
Range: 0.000 to 99999.000
Default: 0.000
Value
Range: 0.000 to 99999.000
Default: 0.000
Value
Range: 0.000 to 99999.000
Default: 0.000
Options
BACK, CANCEL, FINISH (Display returns to Pump Control menu when Wizard
is successfully completed or cancelled. If CANCEL is selected, no changes are
written to the device.)