Page 38 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS 7ML1998MV01
mmmmm
Commissioning
Quick Start Wizards
A Wizard provides an easy step-by-step Quick Start (QS) procedure that configures the
device for a simple application. To configure the SITRANS LUT400 for applications of level,
volume (standard vessel shapes), or flow, use the
Quick Start Wizards via LUI
on page 38 of
this chapter.
Wizards for applications employing more complex vessel shapes are available via
SIMATIC PDM. See
Quick Start (Volume - Linearization)
in the LUT400 Communications
manual
1
.
Other Quick Start Wizards (QSW):
Other Quick Start Wizards using various software packages are also available:
• SIMATIC PDM (HART) (see page 127)
• AMS (HART) (see page 131)
• FC375/475 (HART) (see page 133)
• FDTs (HART) (see page 135)
Before initiating a Quick Start Wizard to configure the device, you may wish to gather the
necessary parameter values. Parameter Configuration Charts that list all parameters and
available options for each application type are available on our website. Go to
www.siemens.com/sitransLUT400
> Support > Application Guides. You can record data
and select from options on the chart that apply to your application, then with this data on
hand, complete the
Quick Start Wizards via LUI
below, or via another Quick Start Wizard,
as referenced above.
Quick Start Wizards via LUI
1) Press to enter Program mode.
RIGHT
arrow
Selecting
options
- Accepts the data (writes the parameter)
- Changes from Edit to Navigation mode
Numeric
editing
- Moves cursor one space to the right
- or with selection highlighted, accepts the
data and changes from Edit to Navigation
mode
LEFT
arrow
:
Selecting
options
Cancels Edit mode without changing the
parameter
Numeric
editing
- Moves cursor to plus/minus sign if this is the
first key pressed
- or moves cursor one space to the left.
- or with cursor on Enter sign, cancels the entry
1.
Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01). (See DVD shipped with
device or download manual from our website.)
Note: Device continues to measure while in Program Mode. If you wish to disable the
device while it is configured, see
3.3.1. Transducer Enable
on page 205.
Key Name Function (Continued)