A5E33329501 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS Page 39
mmmmm
Commissioning
2) Choose Wizards (1.), Quick Start (1.1), and then the appropriate quick start:
QS Level (1.1.1.), QS Volume (1.1.2.), or QS Flow (1.1.3.).
[The QS Flow wizard will display on LUI for LUT430 (Pump and Flow), and LUT440
(OCM) configured models only.]
3) Follow the steps then choose Finish to save Quick Start parameter changes and
return to Program menu, then press three times to return to Measurement
mode.
1. Wizards
1.1. Quick Start
1.1.1. QS Level
Use this wizard to configure simple level applications.
a. Press RIGHT arrow to activate PROGRAM mode and open menu level 1: MAIN
MENU.
b. Press RIGHT arrow two times to navigate to menu item 1.1.1.
c. Press RIGHT arrow to open QS Level.
d. At each step, press DOWN arrow to
accept default values and move directly to
the next item,
or RIGHT arrow to open Edit mode: the
current selection is highlighted.
e. Scroll to desired item and press RIGHT arrow
to store the change, then press DOWN
arrow to continue.
f. At any time, you can press UP arrow to
go back, or LEFT arrow to cancel the wizard.
Notes:
The Quick Start Wizard settings are inter-related and changes apply only after you
choose Finish in the final step.
Perform customization for your application only after the Quick Start has been
completed.
QUICK STARTLEVEL
TRANSDUCER
XRS-5
NEXT
BACK
EDITCANCEL
QUICK STARTLEVEL
NO TRANSDUCER
XPS-10
XPS-15
XCT-8
XCT-12
XRS-5
TRANSDUCER