A5E33329501 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS Page 43
mmmmm
Commissioning
1.1.2. QS Volume
Use this wizard to configure volume applications employing standard vessel shapes.
a. Press RIGHT arrow to activate PROGRAM mode and open menu level 1: MAIN
MENU.
b. Press RIGHT arrow two times to navigate to menu item 1.1.1.
c. Press DOWN arrow and RIGHT arrow to open QS Volume.
d. At each step, press DOWN arrow to accept
default values and move directly to the next item,
or RIGHT arrow to open Edit mode: the
current selection is highlighted.
e. Scroll to desired item and press RIGHT arrow
to store the change, then press DOWN arrow
to continue.
f. At any time, you can press UP arrow to go
back, or LEFT arrow to cancel the wizard.
QUICK STARTVOLUME
TRANSDUCER
XRS-5
NEXT
BACK
EDITCANCEL
QUICK STARTVOLUME
NO TRANSDUCER
XPS-10
XPS-15
XCT-8
XCT-12
XRS-5
TRANSDUCER
Start of QS
Volume Wizard
Select
transducer
Select
temperature source
Select
vessel shape
Set
level units and
setpoints
Set
vessel
dimensions
(vary by vessel)
Set
vessel volume
Volume Wizard
complete
- Transducer
- Temperature source
- Fixed Temperature
- Vessel Shape
- Units
- High Calibration Point
- Low Calibration Point
- Response Rate
- Dimension A
- Dimension L
- Volume Units
- Maximum Volume