A5E33329501 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS Page 93
mmmmm
General Operation
Flow
Flow calculation
The SITRANS LUT400 provides numerous open channel flow calculation features
(see
2.15. Flow
).
The device can be configured to select the flow calculation specific to the primary measuring
device (PMD), such as a flume or weir. If the PMD does not match any of the eleven preset
PMD calculations, a universal flow calculation can be used (PMD = Universal Head
Flow). See
Flow Calculation
on page 267 for more details.
The SITRANS LUT400 converts the head measurement into flow rate. The flow rate is totalized
and stored in a comprehensive data log to facilitate detailed flow analysis.
Totalizing flow
Totalizing of the calculated flow is ongoing. Daily and running totalizers can be viewed in
2.16.
Totalizers
. The daily totalizer resets automatically every 24 hours at 23:59:59, and both can be
reset by the user.
In order to adjust the rate of filling of the totalizer, the
2.7.3.3. Totalizer Multiplier
can be set to
an appropriate value. Totalizing that is specific to a time and date can be viewed under View
Logs for flow (see
3.2.6.2. OCM
on page 203).
The SITRANS LUT400 can be programmed to operate a remote totalizer by assigning any of
the relays to act as a totalizer contact. Under this function, the maximum rate of contact
closure is 5/s with a closure duration of 100 ms.
1
External Totalizers and Flow Samplers
External totalizers are simple counters which count the number of relay clicks produced
by the SITRANS LUT400. This is generally used to keep track of OCM or pumped volume
totals. Note that both of these values are also stored in the SITRANS LUT400 and are
available through communications.
Flow samplers are devices which take a sample of liquid when triggered by a relay click.
These samples are used to monitor water quality over time. Flow samplers can be driven
by OCM volume, pumped volume, or by time depending on the application requirements.
1.
Typically the totalizer should be set for 300 to 3000 counts per day at maximum flow.