A5E33329501 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS Page 161
mmmmm
Parameters
2.7.3.3. Totalizer Multiplier
Use this feature if the LCD Total increments by an amount that is too large
(or too small).
Enter the factor by which actual volume is divided, prior to display on LCD.
Use a value such that the nine-digit totalizer doesn’t roll over between
readings.
Example:
For an LCD Total display in 1000s of volume units, enter
1000.
In this example,
10,000 volume units would display as 10.
2.7.3.4. Inflow/Discharge Adjust
Determines how inflow (or discharge) adjustment is made.
For an illustration, see Pump Totalizers on page 266.
2.7.3.5. Reset Running Totalizer
Select YES to reset pumped volume totalizer value to zero.
Options
.001
.01
.1
*1
10
100
1000
10,000
100,000
1,000,000
10,000,000
Options
*
BASED ON
RATE
ESTIMATION
The inflow rate measured just prior to the start
of the pump cycle is used to estimate the
inflow for the duration of the cycle.
BASED ON
PUMP CYCLE
The inflow is calculated using the change of
volume between the end of the last pump cycle
and the start of the next one, and the time
period between the last cycle and the current
one.
NO ADJUST-
MENT
No inflow adjustment is made (assumes an
inflow of zero).
Options
*NO
YES